Thermokon room regulator 700993

280,39

SKU: Thermokon 700993 Category:

Description

APPLICATION
JOY SR HC AO2DO (85..260 V ~)
The 230 V supplied type AO2DO controls the 230 V heating and cooling valve as a 2-point or thermal 230 V actuator via PWM. The analog output is also used to control a 6-way valve. Two configurable inputs can be used as sensor input, room occupancy or energy lock. In addition to wired valve drives and sensors, sensors and actuators can also be controlled by radio. In addition, as an alternative to wired sensors, an external radio temperature sensor, radio motion detector, a radio temperature sensor for changeover function and radio window contacts/handles can be learnt in. The override by radio is possible by means of higher-level controller profile and cable-bound via Modbus. Radio and wired sensors and actuators are processed identically and can be used in any combination. This guarantees individual and energy-efficient room air conditioning. The device (front of glass in white or black) has a monochrome display and touch-sensitive control buttons. It has a timer with three time channels of four time periods each. Mounting is designed for a flush-mounted box. For hotel applications, the device offers the option of an additional zone (bathroom heating) in conjunction with room temperature sensor and radio actuator SAB.

JOY SR HC 3AO (24 V =/~)
The 24 V supplied type 3AO has three 0..10 V outputs for controlling heating/cooling valves or a 6-way valve. The analog output is also used to control a 6-way valve. Two configurable inputs can be used as sensor input, room occupancy or energy lock. In addition to wired valve drives and sensors, sensors and actuators can also be controlled by radio. In addition, as an alternative to wired sensors, an external radio temperature sensor, radio motion detector, a radio temperature sensor for changeover function and radio window contacts/handles can be learnt in. The override by radio is possible by means of higher-level controller profile and cable-bound via Modbus. Radio and wired sensors and actuators are processed identically and can be used in any combination. This guarantees individual and energy-efficient room air conditioning. The device (front of glass in white or black) has a monochrome display and touch-sensitive control buttons. It has a timer with three time channels of four time periods each. Mounting is designed for a flush-mounted box. For hotel applications, the device offers the option of an additional zone (bathroom heating) in conjunction with room temperature sensor and radio actuator SAB.

TECHNICAL DATA
Measuring values temperature, humidity (optional)
Network technology RS485
Modbus Radio technology EnOcean (IEC 14543-3-10), transmission power <10 mW
Frequency 868 MHz
Measuring range temp 0..+50 °C
Accuracy temperature ±1 °C (typ. at 21 °C)
Measuring range humidity (optional) 0..100% rH non-condensing
Accuracy humidity (optional) ±2% between 10..90% rH (typ. at 21 °C)
Control functions setpoint adjustment +0..+50 °C
Display LCD 60×44 mm, 240×160 px, white backlighting
Functions integrated PI- and 2-point-/ 3-point-controllers, 2nd control loop: 2-point controller, MSG server for 2nd control loop via radio
Enclosure PC and glass, optional black or white
Protection IP30 according to EN 60529
Connection electrical:
* Terminal 1..8 terminal block max. 1,5 mm²
* Terminal 9..12 terminal block max. 1.0 mm²
Ambient condition 0..+50 °C, max. 85% rH non-condensing
Weight 195 g
Mounting flush mounted with standard EU box (Ø=60 mm)
Notes there are 20 EnOcean transmit / receive channels available for various function

JOY SR HC AO2DO (85..260 V ~)
Output voltage 0..10 V =, max. load 5 mA, (for 6-way valves)
Output switch contact 2x normally open contacts (heating/cooling), 240 V max. load 500 mA
Power supply 85..260 V ~
Power consumption max. 2 VA (260 V ~)
Inputs:
* DI 1 input for NTC 10 K or change-over sensor
* DI 2 digital input for non-floating contact (230 V ~)

JOY SR HC AO2DO 3AO (24 V =/~)
Output voltage 3x 0..10 V, max. load 5 mA, 6-way valve control & cooling
Power supply 24 V = (±10%) or 24 V ~ (±10%) SELV
Power consumption max. 1,5 W (24 V =)
Inputs:
*  DI 1 1 input for NTC10K or floating contact
*  DI 2 1 input for floating contact *
Power supply
When several BUS devices are supplied by one 24 V AC voltage supply, it is to be ensured that all “positive” operating voltage input terminals (+) of the field devices are connected with each other and all “negative” operating voltage input terminals (-) (=reference potential) are connected together (in-phase connection of field devices). In case of reversed polarity at one field device, a supply voltage short-circuit would be caused by that device. The consequential short-circuit current flowing through this field my cause damage to it.
Therefore, pay attention to correct wiring
 

Additional information